Ambient condition
Ambient temperature
according to
temperature class T6 -50°C Ta +60°C
Acoustic specification
Volume max. 115 dB(A) reducible in 3 levels
each by 10 dB
Signal tone 32 for each signal level
Delivery condition S0: Tone 24 / S1: Tone 4
Housing degree of protection IP66
Protection class I
Warning Holding time before opening:
10 Min. in case of 230 V
AC
/
2 Min. in case of 24 V
DC
Electric specification
Power consumption max. 14 W
AC Ue = 85 VAC ... 264 VAC
DC Ue = 24 VDC ±20% 19,2 VDC ... 28,8 VDC
Connecting Terminal
Rated cross-section up to 2.5 mm
2
(AWG 14)
Multi-conductor connection max. 2 x 1 mm
2
Tightening torque
for clamp screw 0.4 Nm
Identification on the name plate
FHF Funke + Huster Fernsig GmbH · D-45478 Mülheim an der Ruhr
PTB 12 ATEX 1014
II 2 G Ex d e IIB + H2 T6 Gb
II 2 D Ex tb IIIC T85°C Db0,
-50°C Ta +60°C
Ui = *)………………
Art. no: *)………… F no.: *)………… *) Information variable
WARNING · DO NOT OPEN WHEN ENERGIZED
HAZARD BY ELECTROSTATIC DISCHARGE · JUST DAMP CLEANING
AFTER DE-ENERGIZING, DELAY 10 MINUTES BEFORE OPENING
Technical Specifications
S
tart-up
Fix the device at the wall with two
s
crews (Ø 8 mm).
To correct the distance between the
h
orn and the wall use the supplied
spacer.
Remove the housing cover. If the
setting of the volume and/or signal
tones do not meet your require-
m
ents, you have the following
options according to „Setting of
volume and signal tones
Enter the connecting cable through
t
he cable and wire gland (KLE).
Connect the wires to the clamps
according to connection diagram
(on page 4 + 5). Tighten the housing
cover.
Pull the cable excess of the terminal
compartment through the KLE and
fix the wire with the gland nut of the
KLE.
Setting of volume and signal tone
To set volume and signal tones the
cover of the housing has to be remo-
ved. The electrical plug connection to
the bottom section can be cut. In the
upper section the setting can be
carried out at the 12 slide switches.
The sounder dEV20 disposes of two
signal levels. The signal tone for the
first level is adjusted with the slide swit-
ches 1-5 (S0) according to the signal
choice list. The signal tone for the
second signal level is adjusted with the
slide switches 6-10 (S1).
The volume is set by the slide switches
11 and 12 (see table).
The shift from the first to the second
signal level in case of devices direct
tension is realized by additional appli-
cation of a positive operation voltage
on clamp 3. In case of alternating ten-
sion the shift is made by additional
application of the phase (L1) of the
operation voltage on clamp 3.
After the completion of the setting the
electrical connection to the bottom
section has to be re-established and
the upper section has to be fixed with
the respective screws on the bottom
section. (CAUTION! Don’t damage the
gap of the joint.)
ISO 9001
The information regarding scope of
delivery, application, operation and
operation conditions is current as
of publication date and subject to
change.
Recycling
The complete disposal of the device is
made together with e-waste. When
disassembling the device the compo-
nents polyester, metal and electronics
have to be disposed separately. In any
case please be aware of the disposal
conditions of the specific country.
S
afety instructions
Please read this manual and observe
t
he country-specific assembly stan-
dards as well as the valid safety
i
nstructions and accident prevention
regulations. Intervention at the device
beyond the connection handling is the
exclusive business of the manufacturer.
Reconstructions or changes of the
product are not allowed. The device
shall only be used in a safe and proper
condition. The electrical connection in
the housing shall only be made by
skilled personnel.
Attention ex-area
To comply with the temperature range
i
ndicated on the name plate of the
device, the ambient temperature, ter-
m
inal cross-section as well as the self-
heating of the operating material has to
b
e observed.
The responsibility regarding the inten-
ded use of the sounder, with reference
to the existent general framework in
these instructions shall be exclusively
i
ncumbent on the operating company.
C
are and maintenance
The requirements of EN 60079-17
r
egarding the regular control of the
explosion protection must be applied.
The signalling light contains no service-
able parts.
EC type examination certificate PTB 99 ATEX 3128 X
Ambient temperature Ta: -50°C to +60°C
Thread diameter
Ø
M20 x 1,5
Housing degree of protection IP66
Type of protection Ex e II
Only appropriate tools permitted for the assembly of the KLE!
Cable connection only suitable for static installed wires!
Remarks regarding the cable and wire glands